Product description
Safety-related tactile sensor; Simple and flexible parameter setting; No programming skills required; 18 safe inputs for the redundant inquiry of all common safety sensors; 4 safety semi-conductor outputs; 2 safety relay outputs; 4 optional signalling out
Product Details
- Short circuit detection Yes
- Automatic reset function Yes
- Integral System Diagnostics, status Yes
- Cable section, maximum 2.5 mm²
- Number of fail-safe digital outputs 4
- Ambient temperature, minimum -25 °C
- Overvoltage category III
- No-load supply current I0 500 mA
- Gross weight 300 g
- Earth connection detection Yes
- Enclosure material Polyamide / V0
- Removable Terminals Yes
- Number of fail-safe analogue inputs 2
- Number of signalling outputs 4
- Feedback circuit Yes
- Standards EN ISO 13849-1, IEC 61508, EN 60947-5-1
- Short-circuit recognition Yes
- Number of relay outputs (1-channel) 2
- Terminal designations IEC 61131-2, IEC/EN 60947-1
- Depth 118 mm
- Relative humidity, minimum 15 %
- Degree of pollution to VDE 0100 2
- Required rated short-circuit current to EN 60947-5-1 1,000 A
- Switching thresholds -3 V … 2 V (LOW), 18 V … 28.8 V
- Voltage, Utilisation category DC1 24 VDC
- Climatic stress EN 60068-2-1, EN 60068-2-2, EN 61496
- Reset edge detection Yes
- Number of pulse outputs (test pulse output) 3
- Mounting Snaps onto standard DIN rail to EN 60715
- Number of digital fail-safe in-/outputs 4
- Cable section, minimum 0.25 mm²
- Width 52.5 mm
- Storage and transport temperature, minimum -25 °C
- Degree of protection IP20
- Resistance to vibrations to EN 60068-2-6 10 … 57 Hz, amplitude 0.75 mm
- Operating voltage, maximum 26.4 VDC
- Rated operating current (safety outputs) 700 mA
- Voltage, Utilisation category DC13 24 VDC
- Start input Yes
- Terminal (mechanical) Removable cage terminals
- Mechanical life, minimum 10,000,000 Operations
- Height 100 mm
- Relative humidity, maximum 90 %
- Current, Utilisation category DC1 4 A
- Operating voltage 24 V
- Current leakage Ir 2 mA
- Current, Utilisation category AC-15 3 A
- Switching frequency, maximum 0.1 Hz
- EMC rating EMC-Directive
- Ambient temperature, maximum +55 °C
- Restistance to shock 30 g / 11 ms
- Material of the contacts, electrical Tin
- Integrated Display, Supply Voltage Yes
- Note (Relative humidity) non-condensing
- Current, Utilisation category DC13 4 A
- Versions Limited short-circuit protection, p-type
- Terminal Connector rigid or flexible
- Voltage, Utilisation category AC15 230 VAC
- Storage and transport temperature, maximum +75 °C
- Current consumption at 24V 6 mA
- Start-up test Yes
- Voltage type DC (direct current)
- Current, Utilisation category AC-1 4 A
- Wire breakage detection Yes
- Number of digital fail-safe inputs 14
- Degree of protection of the mounting space IP54
- Current consumption at 24V, maximum 500 mA
- Operating voltage, minimum 21.6 VDC
- Voltage, Utilisation category AC1 250 VAC
- Operating current 100 mA
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
PROTECT-SELECT-CC Related Documents
Manufacturer warranty
PROTECT-SELECT-CC Schmersal
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Fast Shipping & Delivery
We deliver nationwide and international
Secure Payment Processing
Your Safety, Our Priority.
Warranty
Manufacturer warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
About the manufacturer
Applied Automation is an authorized Schmersal distributor, proudly offering a diverse range of innovative safety and automation solutions tailored to meet the rigorous demands of modern industries. Schmersal is a globally renowned manufacturer specializing in the development and production of high-quality safety systems designed to protect both personnel and machinery across various industrial sec...
Recently viewed products
Relevant products
FAQ
Out if stock but available for backorder.
Safety-related tactile sensor; Simple and flexible parameter setting; No programming skills required; 18 safe inputs for the redundant inquiry of all common safety sensors; 4 safety semi-conductor outputs; 2 safety relay outputs; 4 optional signalling out
What can I help you find today?